SEC3004 Fire alarm control panel(火灾报警控制器) 三江
Product Info
The SEC3004 control panels are touch-sensitive,addressable fire detection panels,with up to 4 circuits for the SEC3004,each panel supporting up to 324 addressable points,and are designed to meet the requirements of the EN 54-2&EN 54-4 standards for simple installation,easy operation and easy maintenance.
Product features
EN54-2&EN54-4 certified by LPCB and Applus.
7.0 inch color touch-sensitive screen LCD,resolution of 800×480.
324 addresses for 1 loop,max 4 loops.
A maximum of 5000 fire protection zones are supported.More user-friendly Night Mode Time Range Settings.
Networkable:CAN bus for interconnection of up to 60 FACPs and Ethernet for up to 254 FACPs.
Fire alarm,fault,C&E and operation,each category can store up to 10000 records.
Technical Parameters
| Mains Supply | 110V/230V AC(-15%,+10%),50Hz/60Hz |
| Mains Fuse | T4A250V |
| Operating voltage | 28V±0.5VDC |
| Recommended mains cable | Standard/black mains cable, cable size 1mm² |
| Power rating | Imax.a=3.1A; Imax.b=5.55A; Imin=0.3A |
| Max. battery supply current | 8A(when the Mains is disconnected) |
| Max. charging current | 1A |
| Physical dimensions | 440×400×180mm(2×12V/12Ah Battery) |
| Max. internal resistance of battery | 1Ω |
| Approx.weight(without battery) | 9Kg |
| Battery fuse | 15A |
| Quiescent current (full loaded) | <0.3A |
| S.C.Out (+, -) | Output voltage20~28V DC |
| Max. output current | 1A |
| End of line resistor | 10KΩ |
| Cable diameter | 1mm² ~ 2.5mm² |
| F.A. Out (+, -) | Output voltage20~28V DC |
| Max. output current | 50mA |
| End of line resistor | 10KΩ |
| Cable diameter | 1mm² ~ 2.5mm² |
| Fault Out(NC, COM, NO) | Contact capacity2A@24V DC |
| Cable diameter | 1mm² ~ 2.5mm² |
| AUX 24V (+, -) | Output voltage20~28V DC |
| Max. output current | 2A |
| Cable diameter | 1mm² ~ 2.5mm² |