VRT-300 VESDAnet Socket 威士达Vesda

品牌:威士达

The VESDAnet™ Interface Card (VN Card) is a simple interface card for the range of Xtralis VESDA VLF smoke detectors. The VN Card provides seamless VESDAnet communication from the detector to other VESDAnet devices, including configuration and monitoring tools.
 

What is VRT-300 VESDAnet ?

VESDAnet is a fault-tolerant proprietary Xtralis VESDA communications protocol. VESDAnet allows the Xtralis VESDA range of smoke detectors, displays, programmers and remote units to communicate with each other on one network.

 

Why connect to VRT-300 VESDAnet ?

VESDAnetalsoallowsasystemmanagementpackage(suchasXtralisVSM4)tomonitorandreportonthestatusofalldevicesconnectedonVESDAnet,facilitatingcentralsupervision,managementandcontrolofallXtralisVESDAdetectors.

  RemotedisplaysandrelaysfortheVLFdetector

  ByinstallingaVNCardinaVLFdetector,remotedisplaysandremoterelayscanbeaddedtotheVLF.ThisextendsthecapabilityandflexibilityoftheVLFdetector.

  Features

  •ProvidesseamlessVESDAnetfault-tolerantcommunication

  •Quickandsimpletoinstall

  •Minimalconfigurationrequiredbeforeoperation

  •DiagnosticLEDsgivevisualindicationofthecard’sstatus

  •FullytransferrablebetweenVLFdetectors

  ConnectingVESDAdetectorstobuildingmanagementsystemsorfirepanels

  UsinganappropriateHighLevelInterface(HLI),theinformationonVESDAnetcanbetransmittedto3rdpartymonitoringandcontrolsystemssuchasBuildingManagementSystems(BMS)andFireAlarmControlPanels(FACP).

  Preventingfalsealarmsduetooutsideairpollution

  TheVLFcanbeusedasacosteffectivereferencedetectorforotheractivedetectorsonaVESDAnet.Referencingisatechniqueusedtoreducetheriskofunwantedalarmscausedbyexternalinfluencestoabuilding,suchasairpollution.Itworksbyoffsettingthesignalfromtheactivedetectorintheprotectedareawithareferencesignalfromadetectormonitoringthefreshairintaketothearea.Thisresultsintheactivedetectormeasuringchangesinsmokelevelsthataredueonlytoeventsintheprotectedarea,ratherthanthoseexternaltothearea.  

HavingallXtralisVESDAsmokedetectorsonaVESDAnetloopallowsyoutoconfigureandinterrogateeachdetectorfromacentrallocation,inthiscasetheFacilityManager’soffice.

  Specifications

  PowerConsumption:Consumeslessthan1Wfromthedetectorat24VDC&42mA.

  Dimensions:LengthxWidthxHeight

  137mm(5¼”)x71mm(213/16”)x20mm(13/16”)

  Weight0.08kg(0.176lb)

  Terminals0.2-2.5mm2(30-12AWG)

  OperatingConditions:

  Testedto0to40°C(32to104°F)

  DetectorAmbient0to40°C(32to104°F)

  Humidity5%to95%(non-condensing)

  Compatibility

  IndividualVLFdetectorscanbeinterrogatedandconfiguredbyXtralisVSC,throughtheironboardserialinterface.However,itisnotpossibletoaccessotherdetectorsonVESDAnetthroughthisserialport.

  ToconfiguredevicesviaVESDAnet,anHighLevelInterface(HLI)mustbeconnectedtoaVESDAnetsocket.ThissocketisavailableonVLP,VLSandVLC-505detectors.

  Alternatively,aremoteVESDAnetsocketmodule(VRT-300)providesdirectconnectivitytoanHLIorahandheldprogrammer.Ahand-heldprogrammerorHighLevelInterface(HLI)modulecannotbedirectlyconnectedtoaVLFdetector.